ISOIL Industria Spa
+39.02.660271

Energy meter ML311 ISONRG

The ISONRG ML311 energy meter is an instrument compatible with all types of flow meters: turbine, Woltmann, ultrasound and electromagnetic.

The meter allows you to calculate heating and cooling consumption in an extremely precise way, also by means of an automatic switch which is also useful for cogeneration or trigeneration systems.

It has a logger for up to one year and also acquires signals for cold/hot water sanitary meters or in any case attributable to impulse and/or analog inputs.

It can be used with temperature probes selected in pairs, for the correct and necessary accuracy of the calculation, of the PT100/500/1000 type from 2 to 4 wires.

The energy meter ML311 Isonrg is approved for “financial transactions” according to EN 1434 (MID 004) according to European Directive 2014/32/ EU- and can also transfer data via standard protocols such as RS232, RS485, MODbus, BACnet, Mbus . Pulse and analog I / O.

Range of products that ISOIL Industria can offer directly, with the ISOMAG series of meters produced in its Italian factory, also MID certified.

SKU: 214 Category:
Description
Technical Specifications
Brochure & Data Sheet

The energy meter ML311, electromagnetic flow meters, energy meters, ultrasonic flow meters and systems for industrial automation, have been the passion and continuous research of ISOIL Industria since 1958 and for any information or advice do not hesitate to contact our specialists.

Technical Specifications

  • Case Sealable PPO box
  • Degree of protection IP40/IP54 (with terminal cover)
  • Stand-alone version; DIN rail mounting (acc. DIN60715)
  • Display 4 lines × 15 characters, (9 digit-total. 6 digit-istant.) backlit (blue on request)
  • 6 programmable languages (I, E , S, F, D, P)
  • Special Bi-directional; Double range;
  • Diagnostic; Energy Saving; Switch Hot-Cold; Reset Imputs
  • Pulse outputs /Freq programmable function /Open collector (N 2, 1250 Hz, 100 mA, 40 Vdc – 12,5 KHz opt.)
  • Digital/Analogic imputs
  • Programmable function: 1 Analogic (Flow) 3 Pulses (Hot and cold, liquid and volume)
  • Uscita corrente 1, 0/4 …20 mA – RL = 1000 (i.e. flow rate/power)
  • Data logger 12 mounths (i.e. consumption heating-cooling)
  • Serial Port RS232, RS485, MODBUS, BACNET MS/TP, M-bus, n20pen
  • Accuracy +/- 0.2% v.l. Update calculations every second
  • Repeatability better than 0.1%

Brochure & Data Sheet

Brochure download

Data Sheet download

You may also like…

  • Energy meter for flow meters IFK ISONRG